Procedure
1. Open the inverter according to the inverter‘s instructions.
2. Insert the RJ45 plug into the RJ45 socket on the first inverter.
3. Insert the other end of the cable into the RJ45 socket on second inverter.
4. Connect the other inverters to each other in the same way.
5. Terminate the last inverter according to the inverter instructions.
6. Close the inverter.
Allocate communication address
•
Recommendation: Continuous numbering starting with 1.
Address range 1 - 255.
•
Procedure: Start according to the inverter‘s instructions.